3 Specifications
WIKA operating instructions digital indicator model DI35-M 9
3 Specifications
Specifications
Display
7-segment LED, red, 5-digit, brightness
adjustable in 10 steps
EEPROM (independent of power supply), data
retension > 100 years
Selectable via terminal configuration and
programming
50 ppm/K,
at ambient temperature T < 20 °C or > 40 °C
24 bit, (at measuring time 1 second)
max. 0.1% of totalizator value at integration
time > 1 min
AC 230 V, 50 / 60 Hz, ± 10 % or
{AC 115 V, 50 / 60 Hz, ± 10 %} or
{AC 115 / 230 V, 50 / 60 Hz, ± 10 %
switchable} or
{DC 24 V, ± 10%}
Power supply galvanic insulated
plug-in terminal,
wire cross-section up to 2.5 mm²
1 analogue output (galvanic insulated):
4 ... 20 mA (12-bit), load ≤ 500 Ω or
0 ... 20 mA (12-bit), load ≤ 500 Ω or
0 ... 10 V (12-bit), load ≥ 10 kΩ
0.1% in the range 20 °C ≤ Tu ≤ 40 °C, beyond
this value temperature error 50 ppm/K
100 Ω (at measuring input 0…10 V)