WIKA operating instructions level sensors model RMG
5
13442163.01 06/2010 GB/D/F
Note
The WIKA level transmitters only works correct when mounted in vertical
position. The max. deviation from the vertical is ± 30° and must not be
exceeded.
The oat (6) must be removed before installing the transmitter in
openings with a diameter smaller than the diameter of the oat.
The oat must be marked with „top“.
The oat should be retted inside the tank after installing the level
transmitter and the set collar (7) xed.
4. Electrical connection
Note
All cabling and electrical connections must be carried out in accordance
with the regulations applicable in the country where the equipment is
installed and by personnel qualied to do.
Current spikes may occur Malfunctions by using longer
cable lengths or if the lines are laid together with energy
lines. A screened cable must be used and earthed at one
end.