2.6.7 Measurement of resistance (linear) with two sensors:
PRIMARY_VALUE_UNIT . . . . = Ohm or kOhm
LIN_TYPE. . . . . . . . . . . . . . . . = No linearisation
LIN_TYPE_2
. . . . . . . . . . . . . . = No linearisation
SENSOR_MEAS_TYPE . . . . . = Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION . . . . = 2- or 3-wire
SENSOR_CONNECTION_2
. . = Default set to 2-wire
RJ_TYPE . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
Connections:
2.6.8 Measurement of potentiometer (linear) with one sensor:
PRIMARY_VALUE_UNIT . . . . = %
LIN_TYPE. . . . . . . . . . . . . . . . = No linearisation
LIN_TYPE_2
. . . . . . . . . . . . . . = N/A (ignored in setup check)
SENSOR_MEAS_TYPE . . . . . = PV = SV_1, SV_2 not available
SENSOR_CONNECTION . . . . = 3- or 4-wire
SENSOR_CONNECTION_2
. . = N/A (ignored in setup check)
RJ_TYPE . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
Connections:
2.6.9 Measurement of potentiometer (linear) with two sensors:
PRIMARY_VALUE_UNIT . . . . = %
LIN_TYPE. . . . . . . . . . . . . . . . = No linearisation
LIN_TYPE_2
. . . . . . . . . . . . . . = No linearisation
SENSOR_MEAS_TYPE . . . . . = Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION . . . . = Default set to 3-wire
SENSOR_CONNECTION_2
. . = Default set to 3-wire
RJ_TYPE . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
Connections:
Connections with two sensors
can be configured for
2 measurements, difference,
average or redundancy
Connections with two sensors
can be configured for
2 measurements, difference,
average or redundancy