When the instrument is not yet adjusted, then the display pressure for
100 % corresponds to the nominal measuring range of the sensor (in
the above example 500 mbar).
2 Set the requested mbar value with [->] and [OK].
3 Conrm with [OK] and move to the menu overview with [ESC].
For an adjustment with ow, simply enter the actual measured value
indicated at the bottom of the display.
The max. adjustment is nished.
For level measurement, a linearization is necessary for a ll vessels in
which the vessel volume does not increase linearly with the level - e .g.
in a cylindrical or spherical tank - and the indication or output of the
volume is requested.
Respective linearisation curves are stored for these vessels. They
indicate the relation between the percentage level and the vessel
volume. By activating the suitable curve, the percentage vessel
volume is displayed correctly.
Linearisation curve
linear
Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
In some application, small ow quantities should not be detected. With
the creeping quantity suppression, the ow value can be suppressed
up to a certain % value. The default value is 5 % of the max. ow value,
corresponding to 0.25 % of the max. dierential pressure value. The
limit value is 50 %. This function depends on the selected linearization
function and is only available with root extracted characteristics.
The square root/bidirectional square root characteristics is very steep
at the zero point. This means that small changes in the measured
dierential pressure cause big changes in the output signal. The leak
volume suppression stabilises the signal output.
The DPT10 has two internal totalizers. For both you can adjust volume
or mass as count function as well as separately the unit.
Proceed as follows:
1 Select, for exa mple, menu item "Part su m counter".
Linearization curve with
level
Leak ow volume sup-
pression with ow
Total amounts counter
and subtotalizer with
ow
50 Dierential pressure transmitter DPT10 - metal measuring diaphragm F oundation Fieldbus
6 Adjustment with the indicating and adjustment module