Characteristics linear
Position of the measuring cell constant, in the range: horizontal ±1°
Span based on the zero point
Diaphragm material 316L, Alloy C276, gold rhodium plated, Monel
Filling oil Silicone oil
Material, lateral anges 316L
Inuence of the installation position basic
version
4 mbar
9)10)
A position-dependent zero-point shift can be corrected (see also chapter "General installation
instructions" and "Installation instructions, isolating diaphragm systems").
Deviation determined according to the limit point method according to IEC 60770
11)
Applies to digital interfaces (HART, Probus PA, Foundation Fieldbus) as well as to analogue
current output 4 20 mA. Specications refer to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Reference accuracy - all versions
The following applies to square root extracted characteristics: The accuracy data of DPT10 are
entered with factor 0.5 in the accuracy calculation of the ow.
Reference accuracy - Basic version
10 mbar, 30 mbar measuring cell
- Turn down 1 : 1 ±0.15 % of the set span
- Turn down > 1 : 1 ±0.15 % of the set span x TD
100 mbar measuring cell
- Turn down 1 : 1 up to 4 : 1 ±0.075 % (±0.05 % ) of the set span
- Turn down > 4 : 1 ±(0,012 % x TD + 0.027) of the set span
Measuring cells 500 mbar
- Turn down 1 : 1 up to 15 : 1 ±0.075 % (±0.05 %) of the set span
- Turn down > 15 : 1 ±(0.0015 % x TD + 0.053) of the set span
Reference accuracy - Isolating diaphragm versions
100 mbar measuring cell
- Turn down 1 : 1 up to 4 : 1 ±0.075 % (±0.05 % ) of the set span + inuence of
the isolating diaphragm
- Turn down > 4 : 1 ±(0.012 % x TD + 0.027) of the set span + inuence
of isolating diaphragm
Measuring cells 500 mbar
- Turn down 1 : 1 up to 15 : 1 ±0.075 % (±0.05 %) of the set span + inuence of
the isolating diaphragm
- Turn down > 15 : 1
9)
Instrument is rotated vertically to the diaphragm axis.
10)
For instruments with inert oil, the value doubles.
11)
Incl. non-linearity, hysteresis and non-repeatability.
74 Dierential pressure transmitter DPT10 - metal measuring diaphragm F oundation Fieldbus