Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 11 -
5.2 Main setting mode
Character Name, Description, Setting range Default value
SV
Sets the value for controlled object.
Scaling low limit value to scaling high limit value
(For DC voltage and current inputs, the placement of the decimal
point follows the selection)
0°C
5.3 Sub setting mode
Character Name, Description, Setting range Default value
AT setting
Performs PID auto-tuning. However, when PID auto-tuning does
not finish after 4 hours, PID auto-tuning is shut down compulsory.
PID auto-tuning cancellation :
PID auto-tuning performance :
OUT proportional band setting
Sets the proportional band.
The control action becomes ON/OFF when set to 0.0
Setting range: 0.0 … 110.0%
2.5%
Integral time setting
Sets the integral time.
Setting the value to 0 disables this function.
Not available for ON/OFF action.
Setting range: 0 … 1000 seconds
200 seconds
Derivative time setting
Sets the derivative time.
Setting the value to 0 disables this function.
Not available for ON/OFF action.
Setting range: 0 … 300 seconds
50 seconds
Anti-reset windup setting
Sets anti-reset windup.
Setting the value to 0 disables this function.
Available only for PID action.
Setting range: 0 … 100%
50%
OUT proportional cycle setting
Sets the proportional cycle value for the control output (OUT).
Not available for ON/OFF action or control output analogue
current signal (4 ... 20 mA).
Setting range: 1 … 120 seconds
30 seconds
or 3 seconds
Manual reset setting
Sets the reset value manually.
Available only for P and PD action.
± Proportional band converted value
(For DC voltage and current inputs, the placement of the
decimal point follows the selection)
0.0
Alarm setting
Sets the action point for the alarm output.
Setting the value to 0 or 0.0 disables this function
(excluding Process high and Process low alarms).
When Loop break alarm and Heater burnout alarm are applied
together, the output is common.
Not available when “No alarm action” is selected in Alarm
action selection.
See (Table 5.3-1). (For DC voltage and DC current inputs, the
placement of the decimal point follows the selection.)
0°C