Wika CS4R User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 12 -
.
and
XX.X are
indicated in
turn.
Heater burnout alarm setting
Sets the heater current value for Heater burnout alarm.
Setting the value to 0.0 disables this function.
Self-holding is not available for the alarm output.
Available only when Heater burnout alarm is added.
Rating:
5A [W10] : 0.0 ... 5.0A
10A [W11] : 0.0 ...10.0A
20A [W12] : 0.0 ... 20.0A
50A [W15] : 0.0 ... 50.0A
0.0A
Loop break alarm action time setting
Sets the action time to assess the Loop break alarm.
Setting the value to 0 disables this function.
Setting range: 0 … 200 minutes
0 minutes
Loop break alarm action span setting
Sets the action span to assess the Loop break alarm.
Setting the value to 0 disables this function.
Thermocouple, RTD inputs:
0 … 150°C (°F) or 0.0 … 150.0°C (°F)
DC voltage and current inputs: 0 … 1500
(The placement of the decimal point follows the selection)
0°C
(Table 5.3-1)
Alarm action type Setting range
High limit alarm –(Scaling span) to scaling span
Low limit alarm –(Scaling span) to scaling span
High/Low limits alarm 0 to scaling span
High/Low limit range alarm 0 to scaling span
Process high alarm Scaling low limit value to scaling high limit value
Process low alarm Scaling low limit value to scaling high limit value
High limit alarm with standby –(Scaling span) to scaling span
Low limit alarm with standby –(Scaling span) to scaling span
High/Low limits with standby 0 to scaling span
Minimum
negative
setting value:
–199.9 … –1999
Maximum
positive
setting value:
999.9 … 9999
5.4 Auxiliary function setting mode 1
Character Name, Description, Setting range Default value
Setting value Lock selection
Locks the setting value to prevent setting errors.
The setting item to be locked is dependent on the designation.
PID auto-tuning cannot be carried out when Lock1 or Lock2
is selected.
(Unlock) : All setting values can be changed.
(Lock 1) : None of setting values can be changed.
(Lock 2) : Only main setting mode can be changed.
Unlock
(Lock 3) : All setting values can be changed except Controller/Converter
function selection. However, do not change each setting item of
Auxiliary function setting mode 2.
Changed data reverts to their former value after power is turned
off because they are not saved in the non-volatile memory. Lock
3 is suitable when our programmable controller (with SVTC) is
used together because it has noting to do with memory life.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 30 31

Comments to this Manuals

No comments