Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006 - 25 -
Isolation • Dielectric strength: Circuit isolation configuration
Isolation resistance : 10MΩ or greater at 500V DC
Dielectric strength : 1.5kV AC for 1 minute between input terminal and power terminal
1.5kV AC for 1 minute between output terminal and power terminal
Power supply : 100 … 240V AC 50/60Hz or
24V AC/DC 50/60Hz
Allowable voltage fluctuation range
100 … 240V AC : 85 … 264V AC
24V AC/DC : 20 … 28V AC
Power consumption : Approx. 6VA
Ambient temperature : 0 … 50°C
Ambient humidity : 35 … 85%RH (no condensation)
Mass : Approx.120g
External dimension : 22.5 x 75 x 100mm (W x H x D)
Material : Flame resistant resin (Case)
Color : Light gray (Case)
EVT
CT input
Input
CPU
Isolated
OUTPower supply
Communication
5
98
76
4
3
1 2
* When OUT is logic level DC 0/12 V (non-contact voltage) or
analogue current signal, between OUT and communication
is non-isolated.