Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 21 -
8.3 Event (Alarm) action
8.4 Event (Heater burnout alarm) action
: Event (EVT) output terminals between 8 and 9 is ON
: Event (EVT) output terminals between 8 and 9 is OFF
Event (EVT) output indicator lights up when output terminals between 8 and 9 is ON
and goes out when between them is OFF.
High limit alarm
Alarm
action
Alarm
output
+ side
side
High/Low limits alarm
High/Low limit range alarm
Low limit alarm
Process high alarm
Process low alarm
High limit alarm with standby High/Low limit alarm with standbyLow limit alarm with standby
OFF
ON
A1 hysteresis
OFF
ON
SV
setting
OFF
ON
A1 hysteresis
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Alarm
action
Alarm
action
Alarm
output
Alarm
output
A1 hysteresis
A1 set point
+ side
side
A1 hysteresis A1 hysteresis A1 hysteresis
A1 hysteresis A1 hysteresis A1 hysteresis
A1 set point
A1 set point
SV
setting
A1 set point SV
setting
+ side
side
+ side
side
SV
setting
+ A1 set point
A1 set point SV
setting
SV
setting
+ A1 set point
A1 set point
A1 set point
SV
setting
+ A1 set point
A1 set point A1 set point
A1 set pointA1 set point
A1 set point
A1 set point
Heater burnout
alarm action
ON
OFF
Heater burnout alarm set point
Load current
LargeSmall
Indication
UnlitLit
(EVT) Red
: Event (EVT) output terminals between 8 and 9 is ON.
: Event (EVT) output terminals between 8 and 9 is ON or OFF.
: Event (EVT) output terminals between 8 and 9 is OFF.
: Standby functions in this section.
Event (EVT) output indicator lights up when output terminals between
8 and 9 is ON, and goes out when between them is OFF.