Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 15 -
OUT high limit setting
Sets the OUT high limit value.
Not available for ON/OFF action.
Setting range: OUT low limit value to 105%
Setting greater than 100% is effective to DC
current output type.
100%
OUT low limit setting
Sets the OUT low limit value.
Not available for ON/OFF action.
Setting range: –5% to OUT high limit value
Setting less than 0% is effective to DC current
output type.
0%
OUT ON/OFF action hysteresis setting
Sets the ON/OFF action hysteresis for the OUT.
Available only for ON/OFF action (P=0).
Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection)
1.0°C
Alarm action selection
Selects an alarm action type.
No alarm action :
High limit Alarm :
Low limit alarm :
High/Low limits Alarm :
High/Low limit range Alarm :
Process high Alarm :
Process low Alarm :
High limit alarm with standby :
Low limit alarm with standby :
High/Low limits alarm with standby :
No alarm action
Alarm action Energized/Deenergized
Selects the alarm action Energized/Deenergized.
Not available when “No alarm action” is selected in Alarm action
selection.
Energized :
Deenergized :
Energized
Alarm HOLD function selection
Selects whether alarm HOLD function is [Used] or not.
If alarm HOLD function is set to [Used], once the alarm
functions, alarm output remains until the power is turned off.
Not available when “No alarm action” is selected in Alarm
action selection.
Alarm HOLD [Not used] :
Alarm HOLD [Used] :
Alarm HOLD
[Not used]
Alarm hysteresis setting
Sets the alarm hysteresis.
Not available when “No alarm action” is selected in Alarm action
selection.
Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection.)
1.0°C
Alarm action delayed timer setting
Sets the alarm action delayed time. The alarm is activated
when the setting time has passed after the input enters alarm
output range.
Not available when “No alarm action” is selected in Alarm action
selection.
0 seconds