Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006 - 8 -
• Note
Tighten the terminal screw properly referring to the table below.
Terminal screw Terminal No. Torque
M2.6 1 to 4 Max. 0.5 Nm
M2.0 5 to 9 Max. 0.25 Nm
Terminal arrangement
(Fig. 4-1)
• MAIN OUTPUT : Control output
• EVENT OUTPUT : Outputs when Alarm, Loop break alarm or Heater burnout alarm (option) is ON.
• RS-485 : Serial communication
• TC : Thermocouple
• RTD : Resistance temperature detector
• DC : DC current (DC mA) or DC voltage (DC V)
• Shunt resistor : Shunt resistor 5
0Ω for input signal DC current
• Option: Heater burnout Alarm
(1) This alarm is not available for detecting current
under phase control.
(2) Use the current transformer (CT) provided, and pass a
lead wire of the heater circuit into a hole of the CT.
(3)When wiring, keep the CT wire away from any AC source
or load wires to avoid the external interference.
(Fig. 4-2)
Lower part of main body
CT input
Communication
(RS-485)
CT input socket
Power
supply
Heater
CT
POWER SUPPLY
24V AC/DC
POWER SUPPLY
100 to 240V AC
MAIN OUTPUT
EVENT
OUTPUT
3A
250V AC
0.1A
24V DC
TC
RTD
DC V
DC mA
50Ω
(shunt resistor)
No.1
No.6
No.1
No.6
No.1
No.2
No.5
No.6
No.3
No.4
RS-485
COM
COM
NC
YA(-)
YB(+)
NC