Wika DPT-10 User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
+
1
2
3 3
5 5
6 6
7
4
Fig. 11: Measurement setup, ow measurement in vapours
1 Condensate vessels
2 Orice or impact pressure probe
3 Blocking valves
4 DPT10
5 Precipitator
6 Drain valves
7 3-fold valve block
à Mount DPT10 below the measurement loop so that the eective
pressure lines are always lled with liquid and gas bubbles can
bubble up to the process line
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
à Fill the eective pressure lines to the height of the condensate
vessels before setup
In liquids
Dierential pressure transmitter DPT10 - metal measuring diaphragm Foundation Fieldbus 17
4 Mounting
37246-EN-100120
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 91 92

Comments to this Manuals

No comments