à Mount DPT10 below the lower isolating diaphragm
à The ambient temperature should be the same for both capillaries
Information:
An interface measurement is only possible if the densities of the two
media remain the same and the interface is between the two
measurement points. The total level must be above the upper
measurement point.
1
+
0,3 m
0,8
1,0
Fig. 21: Measurement setup with interface measurement. Min. adjustment with
lling complete with density 0.8 p = 23.5 mbar), max. adjustment with lling
complete with density 1.0 p = 29.4 mbar)
Interface measurement
24 Dierential pressure transmitter DPT10 - metal measuring diaphragm F oundation Fieldbus
4 Mounting
37246-EN-100120